Flexnet inteligente 1 slc, netwrk, prot. mp, ul, fm
Single Loop Networkable Panel Compatible with Mircom Manufactured Devices (MIX-4000) comes with Main Board, Universal Backbox, Red Door, 4 line x 20 character Display, Built-in SLC Loop supporting Mircom Manufactured Devices (Not expandable to more than 1 SLC) Power Supply: 12 Amp Protocol Supported: MGC Multi-Language:
- Menus (English, French, Arabic*, Hebrew*, Chinese*, Russian*, Spanish, Portuguese), and
- Tags (any language supported by Windows 10). *needs DSPL-2440DS or RAXN-4000LCDGC Conventional Adder Module Loops: 2 (Max. of 8 cards per loop) Sub-Addressing: to optimize the number of devices in each loop. Multi-criteria devices reserves a single address on the SLC. Notification Appliances Circuits: 4 Class A/B (Style Z/Y), 1.7 Amps (Each), with Built-in Sync Protocol. Alarm Queues: 4 with selector switches and LEDs for Alarm, Supervisory, Monitor and Trouble Event History Logs: 2 Event Logs, 1 for 5,000 Alarm Events and 1 for 5,000 General Events Panel Configuration: can be done without taking the panel offline. Configuration Files: 3 Files (Current, Previous and Next Configuration) with ""hot-swap"" support Boolean Logic Functions: supported Panel Monitor Utility:
- Real Time Monitoring: Inputs, Outputs, Zones, and System
- Remote Device Activation: for pre-testing inputs/outputs
- Tests Mechanical Equipment on Site: simulates relay output activation
- Supports Main Panel Controls: including System Reset and Signal Silence
- One-Click By-Pass via Software
Order Separately: UDACT-300A (Digital Alarm Communicator), FNC-2000 (Fire Network Controller)"
The base panel includes:
- Main Processor Board with built in Network card interface, Voice Evacuation System Interface, and IP Port for OpenGN Workstation or BMS Integration.
- Four (4) Style Z/Y (Class A/B) Notification Appliance Circuits
- RS485/RS232/Ethernet Communication Ports Software Features:
- Boolean Logic Engine for complex sequences of Operations
- Storage and Management for up to three configuration versions for phased commissioning
- Audio Message Sequencer
- Built in BACNet for BMS System Integration
- Built in Webserver for Remote Event Notification
Features Fire Alarm Control
- Expandable up to 8 SLC
- Sub-addressing to optimize the number of devices in each loop
- Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each with built-in sync protocol
- Supports both 80 character and 960 character back-lit LCD displays with user friendly menu
- Menus and Tags in English, French, Arabic*, Chinese*, Russian*, Spanish and Portuguese. (*needs DSPL-2440 or RAXN-4000LCDG)
- Tags only: it accepts all languages supported by Windows 10 (requires DSPL-2440 or RAXN-4000LCDG)
- Correlatable Switch Inputs which allows for multifunctional outputs
- Four Alarm Queues with selector switches and LEDs for Alarm, Supervisory, Monitor and Trouble
- RS-232 output for remote system printer or terminal
- RS-485 port for system expansion
- Ethernet port for OpenGN workstation or BACNet interface
- Two Event History Logs; one for Alarm-related events and one for all events
- System can be configured without taking the panel off-line
- Supportsthreeconfigurationfiles(current,previousandnext configuration) with “hot swap” support
- Supports Boolean logic functions
- Remote diagnostics via a built-in web server
- UL listed for Smoke Control (UUKL). Network Features
- Up to 63 nodes
- Peer-to-peer network communications
- Fully integrated digital network audio and control over a single pair of copper wire or fiber optic cable (single or multi-mode)
- Remote diagnostics via built-in web server and standard Ethernet port in every node
- Style 4 (Class B) or Style 6 or 7 (Class A) wiring configuration MIX-4000 Devices Features For new or retrofit expansion of existing applications, supports up to 240 MIX-4000 devices per SLC Supports:
- Photo, Heat, and Multi-criteria Sensors
- Optional Built-In Isolation on Sensors
- Multiple Input and Multiple Output modules
- Group activation on the output to speed up actions on the outputs AP Protocol Features Advanced Protocol (AP) supports up to 318 devices per SLC (159 sensors & 159 modules). Supports:
- Smoke, Heat and Fire/CO detection
- 520 Hz sounder base support on both the addressable loop and through the audio/voice evacuation system.
- CLIP mode devices - address range for sensors S1-S99 - address range for modules M1-M99.
- Interrupt operation on input side to speed detection of an event communication back to the panel
- Group activation on the output to speed up actions on the outputs